top of page
Data_Center_heatpump.webp

Heat Pumps for District Heating

Turning Data Centers into District Heating Sources

​

Zepheer is the distributor and service and maintenance partner for European industrial water source heat pumps that lift recovered data center heat to district heating supply temperatures.

​

These solutions are designed for:

​

•⁠  ⁠data centers connecting to district heating networks
•⁠  ⁠district heating operators adding a low-carbon base load heat source
•⁠  ⁠existing plants where data center heat preheats the network return

​

Units are available with ammonia (R717) or isobutane (R600a), natural refrigerants not subject to the EU F-gas phase-down.
 

How It Works

​

Direct-to-chip liquid cooling returns heat at a temperature set by the IT equipment, typically 45-65 °C. District heating networks usually require higher supply temperatures, so the heat is lifted before delivery.

​

Heat transfer path:

​

•⁠  ⁠Zepheer CDU transfers IT heat to the facility water loop
•⁠  ⁠The heat pump evaporator absorbs this heat through a plate heat exchanger
•⁠  ⁠The condenser delivers water at network supply temperature, up to 97°C

​

Because the source is already warm, the temperature lift stays small and the coefficient of performance stays high. The network receives the recovered heat plus the compressor input, so more heat is delivered than the data center produces.
 

Heat Pump Range

​

In response to growing demand from district heating, industrial and data center markets, Zepheer offers the following heat pump solutions:

​

•⁠  ⁠Ammonia (NH3) Water Source Heat Pumps
    Zero GWP natural refrigerant for large-scale base load, from 365 kW to 3.4 MW with supply temperatures up to 90 °C
•⁠  ⁠Isobutane (R600a) Water Source Heat Pumps
    Very low GWP natural refrigerant for high supply temperatures at moderate pressures, from 350 kW to 5.5 MW with supply temperatures up to 97 °C
•⁠  ⁠Heat Exchanger Integration
    Brazed plate heat exchangers separating the data center loop from the heat pump and network circuits
•⁠  ⁠Integrated Controls
    Cooling and heat pump controls configured as one system, with compute cooling always taking priority
•⁠  ⁠Natural Refrigerants 
    Both heat pump ranges are outside the scope of the EU F-gas phase-down
 

Refrigerant Data

​

•⁠  ⁠Ammonia (R717) Properties
    GWP 0, ODP 0, critical point 132.4 °C / 113.6 bar, high latent heat allowing compact heat exchangers
•⁠  ⁠Ammonia (R717) Pressure and Safety
    51 bar saturation pressure at 90 °C condensing, safety class B2L, ventilated machinery room with gas detection per EN 378
•⁠  ⁠Isobutane (R600a) Properties
    GWP 3, ODP 0, critical point 134.7 °C / 36.3 bar, well suited to high condensing temperatures
•⁠  ⁠Isobutane (R600a) Pressure and Safety
    16 bar saturation pressure at 90 °C condensing, safety class A3, low charge design with ATEX-rated components per EN 378
 

Integration Modes

​

The heat pump plant is configured around how the network uses the heat:

​

•⁠  ⁠full lift: all recovered heat raised to network supply temperature
•⁠  ⁠return preheating: data center heat raises the network return temperature before the main heat source
•⁠  ⁠direct supply: when network temperatures allow, heat passes through the heat exchanger with the heat pump bypassed

​

Control logic always gives compute cooling priority, with backup heat rejection sized for periods of low heat demand.

Custom Engineering Approach

​

All heat pump systems are engineered around:

​

•⁠  ⁠data center heat output and cooling loop temperatures
•⁠  ⁠district heating supply and return temperatures
•⁠  ⁠integration with Northern Series, Eremite Series or existing data center halls

​

This ensures the recovered heat matches what the network needs, from design to commissioning.